Analysis of the possibility of using R718 for a heat pump of a heating system based on a liquid-vapor ejector
No Thumbnail Available
Date
2020
Journal Title
Journal ISSN
Volume Title
Publisher
Technology Center
Article
Date of Defense
Scientific Director
Speciality
Date of Presentation
Abstract
The study explores the possibility of using water (R718) as a refrigerant for a heat pump installation of a heating system. This unit is a vapor compression heat pump with a regenerative heat exchanger in which the vacuum unit based on a liquid-vapor ejector is used instead of a scroll refrigeration compressor. The work-ing process of such an apparatus is based on implement-ing a fundamentally new cycle that does not require the supply of working steam from the outside. Instead, steam is generated inside the vacuum unit. The arti-cle describes the proposed installation and its differ-ences from the traditional one, both in terms of circuit solutions and in terms of the operating cycle. A ther-modynamic calculation was performed for the proposed installation with R718 as the working medium and the traditional heat pump systems operating on refriger-ants R142b, R254fa, and R410a. As a result of the cal-culation, the parameters of all the devices included in these schemes were obtained, and the conversion factors of the cycles were determined. To assess the feasibili-ty of using R718 as a working substance and replacing the scroll refrigeration compressor with a liquid-vapor ejector, an exergy analysis was performed. This made it possible to fairly accurately determine the effective-ness of each circuit, since it implemented the possibility of comparing systems using several types of energy (for example, electrical and thermal). As a result, the val-ues of exergetic efficiency of traditional and proposed schemes were obtained. The final stage of the study was the performance of a thermoeconomic analysis. The esti-mated cost was determined for a unit of heat quantity per ton of the product and per unit of the heated area obtained in a unit with the working substance R718 and traditional installations with the working substances R142b, R254fa, and R410a.
Keywords
heat pump unit, heating system, liquid-vapor ejector, exergetic efficiency, thermoeconomic analysis, теплонасосний агрегат, система опалення, ежектор рідинної пари, ексергетична ефективність, термоекономічний аналіз
Citation
Sharapov, S., Husiev, D., Panchenko, V., Kozin, V., & Baha, V. (2020). Analysis of the possibility of using R718 for a heat pump of a heating system based on a liquid-vapor ejector. Eastern-European Journal of Enterprise Technologies, 6(8 (108), 39–44. https://doi.org/10.15587/1729-4061.2020.217274